2-2-2 Conch Aluminum Conductor Triplex Overhead Service Drop Cable Wire

Overhead Neutral-supported Multiplex Conductor:Conch

Code Word: Conch

Size AWG (Phase Conductors): 2

Voltage: 600V

Number of cores: Triplex

Package : Export wooden drum & iron wooden drum or as customer require

Email: manager@hdcable.com.cn

2-2-2 Conch Aluminum Conductor Triplex Overhead Service Drop Cable Wire Application


2-2-2 Conch Aluminum Conductor Overhead Service Drop Cable Wire has three conductors, with one of them being for neutral path, and two electrodes. Used to supply power, usually from a pole-mounted transformer, to the user's service head where connection to the service entrance cable is made. To be used at voltages of 600 volts phase-to-phase or less and at conductor temperatures not to exceed 75°C for polyethylene insulated conductors or 90°C for cross-linked polyethylene (XLPE) insulated conductors. A bare messenger wire of this electrical cable is bonded closely on the two insulated aluminum conductors, which are individually insulated with black cross-linked polyethylene for protection.

2-2-2 Conch Aluminum Conductor Triplex Overhead Service Drop Cable Wire Standard

• B-230 Aluminum Wire, 1350-H19 for Electrical Purposes.
• B-231 Aluminum Conductors, Concentric-Lay-Stranded.
• B-232 Aluminum Conductors, Concentric-Lay-Stranded, Coated Steel Reinforced (ACSR).
• B-399 Concentric-Lay-Stranded 6201-T81 Aluminum Alloy Conductors.
• ICEA S-76-474-Neutral-supported Power Cable Assemblies With Weather-Resistant Extruded Insulation Rated 600Volts
CONSTRUCTION :

2-2-2 Conch Aluminum Conductor Triplex Overhead Service Drop Cable Wire Construction

Phase Conductor

Strand or Compressed 1350-H19 Series Aluminum Conductor.

Neutral(Messenger )Conductor

Bare ACSR messenger. Optional constructions include a messenger of AAC or 6201 alloy.

Insulation

Black Cross Linked Polyethylene (XLP) Insulation.



 
TECHNICAL DATA :

2-2-2 Conch Aluminum Conductor Triplex Overhead Service Drop Cable Wire Technical Data

Rated voltage

V

600

Test voltage

Veff kV/Hz

4/50

Laying temperature

°C

min. -5

Operating temperature

°C

-30 ~ +90

Conductor temperature

°C

max. +90

Short-circuit temperature

°C/s

max. +250 /5

Bending radius (min.)

mm

20 × Ø of cable

 
PARAMETER :
2-2-2 Conch Aluminum Conductor Triplex Overhead Service Drop Cable Wire Parameter 
Code
Word
Phase Conductor Bare Neutral Messenger Weight
Per 1000ft.(Ibs.)
Allowable
Ampacities+
Size
(AWG)
Stranding Insul.
Thick.
(mils)
Size
(kcmil)
Stranding Rated Strength
(Ibs.)
XLP POLY XLP POLY
ACSR NEUTRAL-MESSENGER
Paludina 6 1 45 6 43252 1190 109 109 85 70
Voluta 6 7 45 6 43252 1190 114 114 85 70
Whelk 4 1 45 4 43252 1860 -- 164 115 90
Periwinkle 4 7 45 4 43252 1860 172 172 115 90
Conch 2 7 45 2 43252 2850 262 262 150 120
Neritina 1/0 7 60 1/0 43252 4380 420 420 205 160
Cenia 1/0 9 60 1/0 43252 4380 414 414 205 160
Runcina 2/0 7 60 2/0 43252 5310 520 520 235 185
Triton 2/0 11 60 2/0 43252 5310 512 512 235 185
Mursia 3/0 17 60 3/0 43252 6620 635 635 275 215
Zuzara 4/0 18 60 4/0 43252 8350 789 789 315 245
Limpet 336.4 19 80 336.4 43118 8680 1167 1167 420 325
 