35mm 4 Core Steel Wire Armoured SWA Cable Application
35mm 4 Core Steel Wire Armoured SWA Cable made up of a black PVC sheath, XLPE insulation, copper conductors and steel wire armouring. This type of cable is designed for mains electricity in various applications, including laying underground, power networks, incoming mains to homes amongst a host of other uses externally and internally.
35mm 4 Core Steel Wire Armoured SWA Cable is suitable and often used for direct burial, with the steel wire armouring providing further protection from external damaged. The XLPE insulation is resistant to a number of different fluids, chemicals and has good heat stability, as well as being UV Resistant.
35mm 4 Core Steel Wire Armoured SWA Cable Standard
BS 5467, IEC/EN 60502-1, IEC/EN 60228 , Flame Retardant according to IEC/EN 60332-1-2
35mm 4 Core Steel Wire Armoured SWA Cable Construction
Conductors: Plain circular, compacted or shaped stranded copper or aluminium conductor (Conductor shaped: RE=circular solid, CC=compacted circular stranded, SM=sector shaped stranded)
Insulation: XLPE (cross-linked polyethylene) rated at 90°C
Color identification
1 Core : Red or Black, 2 Cores : Red, Black, 3 Cores: Red, Yellow, Blue , 4 Cores: Red, Yellow, Blue, Black, 5 Cores: Red, Yellow, Blue, Black, Green
Above 5 Cores: Black Cores with White numerals
*The above identifying can be changed as user requirement
Assembly /Inner Sheath:Two, Three or Four insulated conductors are laid-up together with non-hygroscopic fillers and the assembly is bedded with an extruded layer of PVC. In case of non-armoured cables, this layer may be omitted
Armour: Galvanized Steel Wires, single core cables shall be Aluminium wire armour, Aluminum/Steel Tapes applied helically over the bedding of multi-core cables as per IEC 60502.
Sheath:Extruded PVC Type ST2 as per IEC 60502-1 or Type 9 as BS 6346/5467.
Special type of PVC sheathing material such as Fire Retardant PVC, Anti-Termite PVC, Anti-Rodent PVC, Sunlight resistant PVC, Oil Resistant PVC are available on special request. Also, special sheathing materials such as LLDPE, MDPE, HDPE, LSZH, and CPE are available on request.
Fire Performance of Cable Sheaths
Cables can be supplied with special flame retardant PVC outer sheath to comply With the flame test requirements of IEC 60332-3-22, IEC 60332-3-23 and IEC 60332-3-24, we can also supply cables with Low Smoke Halogen Free (LSHF) material according to IEC 60502-1, BS 7211, BS 6724 or other equivalent standards.
35mm 4 Core Steel Wire Armoured SWA Cable Technical Data
Voltage: 600/1000v
Operating temperature: Maximum 90°C, minimum bending 0°C
Maximum short-circuit temperature: 250°C(max. 5s)
Minimum bending raduis: x20 cable diameter (armoured)
35mm 4 Core Steel Wire Armoured SWA Cable Parameter
Approx overall diameter (approximate size) |
28.8mm |
Approx weight per meter |
2.3 Kg |
Armour / Protection |
SWA |
Bedding |
PVC (Polyvinyl-Chloride) |
BS Number |
BS5467 |
Colour |
Black |
Conductors |
Plain annealed stranded copper |
Core identification |
4 core (Brown, Black, Grey and Blue) |
Current Rating |
154A |
Insulation |
XLPE (Cross linked polyethylene) |
Operating temperature |
Maximum 90C, minimum bending 0C |
Sheath / Jacket |
PVC (Polyvinyl-Chloride) |
Standard |
BS5467: Electric cables. Thermosetting insulated, armoured cables for voltages of 600/1000V and 1900/3300V |
Voltage |
600 / 1000V |