NFC 33-209 Aerial Bundle Conductor ABC Cable 4x16mm2

4x16mm2 ABC Cable Overhead Line with Aluminum Conductor XLPE Insulation

Conductor: Stranded Round Aluminum Conductor

Insulation : XLPE

Voltage : 0.6/1kV

Number of cores: 4 cores

Package : Export wooden drum & iron wooden drum or as customer require

Email: manager@hdcable.com.cn

ABC Cable 4x16mm2 Application

4x16mm2 ABC Cable Aerial Bundle Cable Aluminum Insulated Twist Cable used to supply power,usually from a pole-mounted transformer, to the user's service head where connection to the service entrance.To be used at 600V or less phase to phase and at conductor temperatures not to exceed 75°C for polyethylene insulated or 90°C for cross linked.


ABC Cable 4x16mm2 Standard

Aerial Bundled Conductors are manufactured to National French Standard NFC 33-209.
CONSTRUCTION :
 
4 core 16mm2 abc cable

Phase Conductor

Aluminium conductor, round stranded compressed (RM).

Neutral Conductor

Alloy aluminium conductor  round stranded compressed (RM).

Insulation

XLPE & HDPE

Assembly

Cores and the neutral, conductor stranded together in right-hand lay, additionally 1, 2 or 3 cores of reduced cross section can be co-stranded.

 
TECHNICAL DATA :

Rated voltage

kV

0.6/1

Test voltage

Veff kV/Hz

4/50

Laying temperature

°C

min. -5

Operating temperature

°C

-15 ~ +90

Conductor temperature

°C

max. +90

Short-circuit temperature

°C/s

max. +250 /5

Bending radius (min.)

mm

15 × Ø of cable

  

PARAMETER :

ABC Cable 4x16mm2 Parameter

TECHNICAL DATA SHEET

Câble préassemblé torsadé 4x16mm²

No.

Description

Unit

Data Provided

1

Standards Reference

 

IEC 60502-1,NFC 33-209

2

Voltage

Volt

600/1000

3

Type of cable

mm²

4x16

4

Material of conductor

 

Stranded Aluminum wire

Stranding no. of wires in conductor

No.

7

Approx.diameter of conductor

mm

5.0

5

Material of insulation

 

Black XLPE

Norminal thickness of insulation

mm

1.2

Approx.diameter of insulated conductor

mm

7.50

6

Approx.overall diameter of completed cable

mm

18.0

7

Maximum d.c. resistance of conductor of cable at 20°C

ohm/km

1.91

8

Approx.weight of completed cable

kg/km

263