Send message
SEND
RESET
+86 371 60975619
manager@hdcable.com.cn
+8613290961076
5 Core Armoured Cable Copper Cu XLPE PVC SWA PVC BS5467 0.6/1kV

5 Core Armoured Cable Copper XLPE PVC SWA 0.6/1kV

Voltage Rating: 600/1000 Volts,

Conductor: soft annealed copper

Insulation: Cross Linked Poly Ethylene (XLPE)

Armour: Steel Wire Armoured

Oversheath: PVC

Email: manager@hdcable.com.cn

5 Core SWA Armoured Cable Application

These cables are used for electricity supply in low voltage installation system, They are suitable for installation in indoors and outdoors, in cable ducts, under ground, in power and switching stations, local energy distributions, industrial plants, where there is no risk of mechanical damage. The lead sheath brings an enhanced resistance to aromatic hydrocarbons.

5 Core SWA Armoured Cable Standard

BS 5467 IEC 60502-1. 
CONSTRUCTION :

Conductor Plain cicrcular, compacted or shaped stranded copper or aluminum conductor, conform to IEC 60228 class 2
Insulation XLPE (cross-linked polyethylene), rated at 90°C
Bedding PVC (Polyvinyl Chloride)
Armour SWA (Galvanized Steel Wire Armour)
Sheath PVC (Polyvinyl Chloride)
Rated Voltage 600/1000V
5 core swa cable 
TECHNICAL DATA :

5 Core SWA Armoured Cable Technical Data

STANDARD IEC 60502-1, BS 5467 and BS 6346
APPLICATION Distribution networks, Industrial use
CHEMICAL PERFORMANCE Chemical & Oil resistance: Good
MECHANICAL PERFORMANCE Minimum bending raduis: x15cable diameter (unarmoured)
Minimum bending raduis: x20 cable diameter (armoured)
FIRE PERFORMANCE Flame non-propagation base on IEC 60332-1
Reduced emission of Halogens chlorine<15%
TERMINAL PERFORMANCE Maximum service temperature: 90°C
Maximum short-circuit temperature: 150°C(max. 5s)
Minimum service temperature: -40°C
 

 
PARAMETER :

5 Core SWA Armoured Cable Parameter

0.6/1kV-5 core copper conductor XLPE insulated steel wire armored PVC sheathed power cable
Nominal cross sectional area Insulation thickness Steel Wire diameter Sheath thickness Approximate outer diameter Approx.
weight
Max.D.C resistance of conductor(20℃) Current carrying capacity 
mm2 mm mm mm mm kg/km Ω/km In Air(A) In Ground(A)
5X2.5 0.7 1.25 1.8 17.9 645 7.41 20 27
5X4 0.7 1.25 1.8 19.1 770 4.61 26 36
5X6 0.7 1.25 1.8 20.5 925 3.08 33 45
5X10 0.7 1.6 1.8 24.6 1417 1.83 46 60
5X16 0.7 1.6 1.8 27.6 1812 1.15 59 77
5X25 0.9 1.6 1.9 32.2 2460 0.727 77 98
5X35 0.9 1.6 2 34.1 3019 0.524 95 119
5X50 1 2 2.2 39.7 4166 0.387 119 144
5X70 1.1 2 2.3 44.9 5443 0.268 151 175
5X95 1.1 2.5 2.5 51.3 7485 0.193 186 210
5X120 1.2 2.5 2.7 55.9 9026 0.153 217 242
5X150 1.4 2.5 2.8 61.4 10912 0.124 245 270
5X185 1.6 2.5 3 67.6 13119 0.0991 284 305
5X240 1.7 2.5 3.3 74.8 16427 0.0754 336 350
5X300 1.8 3.15 3.5 83.2 20915 0.0601 389 396
 
Send message