Aerial Insulated Cable (IEC 60502-2)

Conductor: Circular compressed aluminum, aluminum-alloy, copper.

Conductor shield: Semi-conducting cross-linked polyethylene.

Insulation: Cross-linked polyethylene (Natural)

Sheath: PE & XLPE

Package : Export wooden drum & iron wooden drum or as customer require

Email: manager@hdcable.com.cn

Cable Application:

Aerial Insulated Cables with voltages of 10kV.The products primarily used for the distribution of electrical energy under normal conditions of overhead (aerial) installations.The conductors must be installed on insulators and/or spacers adequate for the service voltage. The user may want to give consideration to the dielectric compatibility of the covering, insulator, spacer etc.

Description

The conductors are stranded,circular compressed aluminum, aluminum-alloy, copper. The conductor screen is the extruded Semi-conducting conductor shield in Black. And the outer Insulation is mainly thermoplastic polyethylene (PE) or cross-linked polyethylene (XLPE) in Black with Weather or UV resistant. This standard covers both thermoplastic and cross linked polyethylene constructions, rated for 75°C or 90°C normal service temperature.
SPECIFICATION :

GB/T 14049 (Equal to IEC 60502-2) Aerial Insulated Cables For Rated Voltage of 10kV

Type No. of Cores Nominal size
mm²
CU/XLPE,AAC/XLPE,AAAC/XLPE 1 10 ~ 400
3 25 ~ 400
3+k(A) or 3+k(B) 25 ~ 400 ; k:25~120
CU/PE,AAC/PE,AAAC/PE,CU/XLPE,AAC/XLPE,AAAC/XLPE 1 10 ~ 400
AAC/XLPE,AAAC/XLPE 3 25 ~ 400
3+k(A) or 3+k(B) 25 ~ 400 ; k:25~120
The k is a load-bearing core. (A) means steel carrying stranded wire, (B) means aluminum alloy carrying stranded wire.
Parameter-Copper Conductor :
10kV Aerial Insulated Cables
Nominal Size Min. No.
of Wires
Approx. Diameter of Conductor Min.
Thickness of Conductor screen
(Approx.)
Nominal Thickness of Insulation Nominal Thickness of Insulation Screen Min. Breaking Load
Reduced Nominal Hard Copper Soft Copper Hard Copper
mm² No. mm mm mm mm Ω/km Ω/km N
10 6 3.8 0.5 - 3.4 - 1.830 -
16 6 4.8 0.5 - 3.4 - 1.150 -
25 6 6.0 0.5 2.5 3.4 0.749 0.727 8465
35 6 7.0 0.5 2.5 3.4 0.540 0.524 11731
50 6 8.3 0.5 2.5 3.4 0.399 0.387 16052
70 12 10.0 0.5 2.5 3.4 0.276 0.268 23461
95 15 11.6 0.6 2.5 3.4 0.199 0.193 31759
120 18 13.0 0.6 2.5 3.4 0.158 0.153 39911
150 18 14.6 0.6 2.5 3.4 0.128 - 49505
185 30 16.2 0.6 2.5 3.4 0.1021 - 61846
240 34 18.4 0.6 2.5 3.4 0.0777 - 79823
300 34 20.6 0.6 2.5 3.4 0.0619 - 99788
400 53 23.8 0.6 2.5 3.4 0.0484 - 133040
 
Parameter-AAC AAAC Conductor :
 10kV Aerial Insulated Cables 
Nominal Size Min. No.
of Wires
Approx. Diameter of Conductor Min.
Thickness of Conductor Screen
(Approx.)
Nominal Thickness of Insulation Nominal Thickness of Insulation Screen Min. Breaking Load
Reduced Nominal AAC AAAC AAC AAAC
mm² No. mm mm mm mm Ω/km Ω/km N N
10 6 3.8 0.5 - 3.4 3.080 3.574 - -
16 6 4.8 0.5 - 3.4 1.910 2.217 - -
25 6 6.0 0.5 2.5 3.4 1.200 1.393 3762 6284
35 6 7.0 0.5 2.5 3.4 0.868 1.007 5177 8800
50 6 8.3 0.5 2.5 3.4 0.641 0.744 7011 12569
70 12 10.0 0.5 2.5 3.4 0.443 0.514 10354 17596
95 15 11.6 0.6 2.5 3.4 0.320 0.371 13727 23880
120 18 13.0 0.6 2.5 3.4 0.253 0.294 17339 30164
150 18 14.6 0.6 2.5 3.4 0.206 0.239 21033 37706
185 30 16.2 0.6 2.5 3.4 0.164 0.190 26732 46503
240 34 18.4 0.6 2.5 3.4 0.125 0.145 34679 60329
300 34 20.6 0.6 2.5 3.4 0.100 0.116 43349 75411
400 53 23.8 0.6 2.5 3.4 0.0778 0.0904 55707 100548
Parameter- ACSR/AW-OC :
 22.9kV ACSR/AW-OC Aerial Insulated Cables  
Size
(mm²)
No. and Dia.
of Wires
Conductor Diameter Insulation Thickness Cable Diameter Rated
Strength
Weight
AL St
No. No. /mm mm mm mm kgf kg/km
22.9 kV ACSR/AW-OC/XLPE
32 6/SB 1/2.6 7.2 3.0 13.2 1090 210
58 6/SB 1/3.5 9.7 3.0 15.7 1900 330
95 6/SB 1/3.5 12.0 3.5 19.0 2360 530
160 18/SB 1/3.2 15.4 4.0 23.4 3080 730
240 18/SB 1/4.0 18.9 4.0 27.0 4500 1040