Send message
SEND
RESET
+86 371 60975619
manager@hdcable.com.cn
+8613290961076
Your position: 
AAC-All Aluminum Stranded Conductor BS 215 Part1

British Standard BS 215 Part1 AAC All Aluminum Stranded Conductor

Shape of conductor: circular and sectional

Sectional area: 22 - 400mm2

Insulation: N/A

Standard: BS 215 part1

Email: manager@hdcable.com.cn

All Aluminum Stranded Conductor BS 215 Part 1 Application


AAC conductor is also called aluminium stranded conductor.This British Standard applies to aluminium stranded conductors for overhead power transmission.Aluminium wires used in the construction of the conductor is material GIE in the H9 condition as specified in BS 26273. These conductors can be used for a variety of voltages such as low, medium and high voltage. AAC is now also widely used in urban areas where short spans and high electrical conductivity are required.

STANDARD :

All Aluminum Stranded Conductor BS 215 Part 1 Standard

According to BS 215 Part 1:1970, Aluminium conductors and aluminium conductors, steel reinforced for overhead power transmission. Part 1: Aluminium stranded conductors
Construction :

All Aluminum Stranded Conductor BS 215 Part 1 Construction


Stranded conductor

a conductor consisting of seven or more aluminium wires of the same nominal diameter twisted together in concentric layers. When the conductor consists of more than one layer, successive layers are twisted in opposite directions

Diameter
the mean of two measurements at right angles taken at the same cross section direction of lay the direction of lay is defined as right-hand or left-hand. With right-hand lay, the wires conform to the direction of the central part of the letter Z when the conductor is held vertically. With left-hand lay, the wires conform to the direction of the central part of the letter S when the conductor is held vertically

lay ratio
the ratio of the axial length of a complete turn of the helix formed by an individual wire in a stranded conductor to the external diameter of the helix For other definitions reference should be made to BS 2052).



AAC-All Aluminum Stranded Conductor BS 215 part1

PARAMETER :
CODE NOMINAL AREA STRANDING OVERALL DIAMETER WEIGHT RATED STRENGTH ELECTRICAL RESISTANCE CURRENT RATING*
NOMINAL TEORICAL
  MM² MM² NO.×MM MM KG/KM KN Ω/KM A
Midge 22 23.33 7/2.06 6.18 64 3.99 1.227 106
Gnat 25 26.8 7/2.21 6.6 73.8 4.83 1.0643 122
Mosquito 35 37 7/2.59 7.8 102.1 6.27 0.7749 141
Ladybird 40 42.8 7/2.79 8.4 117.9 7.28 0.6678 157
Ant 50 52.83 7/3.1 9.3 145 8.28 0.5419 175
Fly 60 63.55 7/3.4 10.2 174 9.9 0.4505 196
Wasp 100 106 7/4.39 13.17 290 16 0.2702 268
Hornet 150 157.6 19/3.25 16.25 434 25.7 0.1825 342
Charfer 200 213.2 19/3.78 18.9 587 35.4 0.1349 412
Cockroach 250 265.7 19/4.22 21.1 731 40.4 0.1083 471
Butterfly 300 322.7 19/4.65 23.25 888 48.75 0.08916 530
Centipede 400 415.2 37/3.78 26.46 1145 63.1 0.06944 616
Maybug 475 486,1 37/4,09 28,6 1342 74.01 0,05931 740
Scorpion 500 529,8 37/4,27 29,9 1460 79.98 0,05441 887
Cicada 600 628,3 37/4,65 32,6 1733 94.95 0,04588 1056
Note: *The values of current rating mentioned in above Table are based on wind velocity of 0.6 metre/second, solar heat radiation of 1200 watt/metre2, ambient temperature of 50° C & conductor temperature of 80°C. 
Send message