×
Send message
SEND
RESET
+86 371 60975619
manager@hdcable.com.cn
+8613290961076
All Aluminum Stranded Conductor AAC Fly 60mm2

BS 215 Part 1 All Aluminum Conductor AAC Fly 60mm2

Code Word: Fly

Number of Stranded: 7

Conductor Material: All Aluminum Conductor

Standard: BS 215 Part 1

Email: manager@hdcable.com.cn

AAC Conductor Fly 60mm2 Application


AAC Conductor Fly 60mm2 can be used in low and medium voltage overhead lines. It’s commonly used in urban areas because of its ability to carry significant voltages over short distances. The long-lasting, corrosion resistant qualities of aluminum make this conductor a popular choice for use in coastal areas as well as for use in the railway and subway industries. Shipyards and offshore construction sites benefit from the conductor’s durability. AAC Conductor Fly 60mm2 can be used for most overhead transmission duties when conductor strength is not a factor. The conductor can also be used for primary and secondary distribution applications.

AAC (all aluminum conductor) is the most economical bare overhead conductor due to its lighter weight. It offers easier handling during installation and use of simpler fittings. The wire is corrosion resistant due to its homogeneous construction.
STANDARD :

AAC Conductor Fly 60mm2 Standard

According to BS 215 Part 1:1970, Aluminium conductors and aluminium conductors, steel reinforced for overhead power transmission. Part 1: Aluminium stranded conductors
CONSTRUCTION :

AAC Conductor Fly 60mm2 Construction

The aluminium wires used in the construction of the conductor shall be material GIE in the H9 condition as specified in BS 26273). a conductor consisting of seven or more aluminium wires of the same nominal diameter twisted together in concentric layers. When the conductor consists of more than one layer, successive layers are twisted in opposite directions

AAC Poppy Conductor

PARAMETER :
Code Word:
Fly
Nominal Area (mm2): 60
Calculate Area (mm2) 63.55
Stranding: 7
Diameter Individual Wire Aluminum (mm): 3.4
Overall Diameter (O.D.) (mm): 10.2
Weight Per 1000 Meters (kg): 174
Rated Strength (KN): 9.9
Resistance DC 20°C Per 1000 Meters (Ω): 0.4505
Allowable Ampacity  (Amps): 196
Send message
SEND
RESET
Related products