Copper cable with galvanized steel wire armoured
Voltage Rating: 600/1000 Volts,
Conductor: soft annealed copper
Insulation: Cross Linked Poly Ethylene (XLPE)
Armour: Steel Wire Armoured
Oversheath: PVC
Email: manager@hdcable.com.cn
Conductor | Plain cicrcular, compacted or shaped stranded copper or aluminum conductor, conform to IEC 60228 class 2 |
Insulation | XLPE (cross-linked polyethylene), rated at 90°C |
Bedding | PVC (Polyvinyl Chloride) |
Armour | SWA (Galvanized Steel Wire Armour) |
Sheath | PVC (Polyvinyl Chloride) |
Rated Voltage | 600/1000V |
STANDARD | IEC 60502-1, BS 5467 and BS 6346 |
APPLICATION | Distribution networks, Industrial use |
CHEMICAL PERFORMANCE | Chemical & Oil resistance: Good |
MECHANICAL PERFORMANCE | Minimum bending raduis: x15cable diameter (unarmoured) Minimum bending raduis: x20 cable diameter (armoured) |
FIRE PERFORMANCE | Flame non-propagation base on IEC 60332-1 Reduced emission of Halogens chlorine<15% |
TERMINAL PERFORMANCE | Maximum service temperature: 90°C Maximum short-circuit temperature: 150°C(max. 5s) Minimum service temperature: -40°C |
0.6/1kV-2 core copper conductor XLPE insulated steel wire armored PVC sheathed power cable | ||||||||
Nominal cross sectional area | Insulation thickness | Steel Wire diameter | Sheath thickness | Approximate outer diameter | Approx. weight |
Max.D.C resistance of conductor(20℃) | Current carrying capacity | |
mm2 | mm | mm | mm | mm | kg/km | Ω/km | In Air(A) | In Ground(A) |
2X2.5 | 0.7 | 0.8 | 1.8 | 14.8 | 364 | 7.41 | 23 | 32 |
2X4 | 0.7 | 0.8 | 1.8 | 15.7 | 425 | 4.61 | 30 | 41 |
2X6 | 0.7 | 1.25 | 1.8 | 17.6 | 646 | 3.08 | 39 | 53 |
2X10 | 0.7 | 1.25 | 1.8 | 20.1 | 802 | 1.83 | 53 | 70 |
2X16 | 0.7 | 1.25 | 1.8 | 22.3 | 1008 | 1.15 | 68 | 91 |
2X25 | 0.9 | 1.6 | 1.8 | 26.3 | 1470 | 0.727 | 91 | 116 |
2X35 | 0.9 | 1.6 | 1.8 | 27.6 | 1712 | 0.524 | 112 | 140 |
2X50 | 1 | 1.6 | 1.9 | 30.8 | 2123 | 0.387 | 137 | 168 |
2X70 | 1.1 | 2 | 2 | 35.4 | 2974 | 0.268 | 172 | 203 |
2X95 | 1.1 | 2 | 2.1 | 39.5 | 3737 | 0.193 | 214 | 249 |
2X120 | 1.2 | 2 | 2.3 | 42.9 | 4453 | 0.153 | 249 | 284 |
2X150 | 1.4 | 2.5 | 2.4 | 48 | 5744 | 0.124 | 284 | 315 |
2X185 | 1.6 | 2.5 | 2.6 | 52.7 | 6811 | 0.0991 | 326 | 357 |
0.6/1kV-3 core copper conductor XLPE insulated steel wire armored PVC sheathed power cable | ||||||||
Nominal cross sectional area | Insulation thickness | Steel Wire diameter | Sheath thickness | Approximate outer diameter | Approx. weight |
Max.D.C resistance of conductor(20℃) | Current carrying capacity | |
mm2 | mm | mm | mm | mm | kg/km | Ω/km | In Air(A) | In Ground(A) |
3X2.5 | 0.7 | 0.8 | 1.8 | 15.3 | 405 | 7.41 | 20 | 27 |
3X4 | 0.7 | 0.8 | 1.8 | 16.2 | 481 | 4.61 | 26 | 36 |
3X6 | 0.7 | 1.25 | 1.8 | 18.3 | 696 | 3.08 | 33 | 45 |
3X10 | 0.7 | 1.25 | 1.8 | 20.9 | 930 | 1.83 | 46 | 60 |
3X16 | 0.7 | 1.25 | 1.8 | 23.3 | 1191 | 1.15 | 59 | 77 |
3X25 | 0.9 | 1.6 | 1.8 | 27.6 | 1745 | 0.727 | 77 | 98 |
3X35 | 0.9 | 1.6 | 1.8 | 29 | 2100 | 0.524 | 95 | 119 |
3X50 | 1 | 1.6 | 1.9 | 32.5 | 2628 | 0.387 | 119 | 144 |
3X70 | 1.1 | 2 | 2.1 | 37.9 | 3728 | 0.268 | 151 | 175 |
3X95 | 1.1 | 2 | 2.2 | 41.8 | 4692 | 0.193 | 186 | 210 |
3X120 | 1.2 | 2 | 2.3 | 45.5 | 5645 | 0.153 | 217 | 242 |
3X150 | 1.4 | 2.5 | 2.5 | 51.3 | 7350 | 0.124 | 245 | 270 |
3X185 | 1.6 | 2.5 | 2.7 | 55.9 | 8698 | 0.0991 | 284 | 305 |
3X240 | 1.7 | 2.5 | 2.9 | 62.1 | 10837 | 0.0754 | 336 | 350 |
3X300 | 1.8 | 2.5 | 3 | 67.4 | 12990 | 0.0601 | 389 | 396 |
0.6/1kV-4 core copper conductor XLPE insulated steel wire armored PVC sheathed power cable | ||||||||
Nominal cross sectional area | Insulation thickness | Steel Wire diameter | Sheath thickness | Approximate outer diameter | Approx. weight |
Max.D.C resistance of conductor(20℃) | Current carrying capacity | |
mm2 | mm | mm | mm | mm | kg/km | Ω/km | In Air(A) | In Ground(A) |
4X2.5 | 0.7 | 0.8 | 1.8 | 16.1 | 472 | 7.41 | 20 | 27 |
4X4 | 0.7 | 1.25 | 1.8 | 18.1 | 677 | 4.61 | 26 | 36 |
4X6 | 0.7 | 1.25 | 1.8 | 19.3 | 804 | 3.08 | 33 | 45 |
4X10 | 0.7 | 1.25 | 1.8 | 22.3 | 1088 | 1.83 | 46 | 60 |
4X16 | 0.7 | 1.6 | 1.8 | 25.7 | 1571 | 1.15 | 59 | 77 |
4X25 | 0.9 | 1.6 | 1.8 | 29.7 | 2085 | 0.727 | 77 | 98 |
4X35 | 0.9 | 1.6 | 1.9 | 31.4 | 2543 | 0.524 | 95 | 119 |
4X50 | 1 | 1.6 | 2 | 35.3 | 3214 | 0.387 | 119 | 144 |
4X70 | 1.1 | 2 | 2.2 | 41.2 | 4571 | 0.268 | 151 | 175 |
4X95 | 1.1 | 2 | 2.3 | 45.6 | 5782 | 0.193 | 186 | 210 |
4X120 | 1.2 | 2.5 | 2.5 | 51.2 | 7557 | 0.153 | 217 | 242 |
4X150 | 1.4 | 2.5 | 2.7 | 56.1 | 9080 | 0.124 | 245 | 270 |
4X185 | 1.6 | 2.5 | 2.8 | 61.3 | 10822 | 0.0991 | 284 | 305 |
4X240 | 1.7 | 2.5 | 3.1 | 68.1 | 13566 | 0.0754 | 336 | 350 |
4X300 | 1.8 | 2.5 | 3.2 | 74.1 | 16356 | 0.0601 | 389 | 396 |
0.6/1kV-5 core copper conductor XLPE insulated steel wire armored PVC sheathed power cable | ||||||||
Nominal cross sectional area | Insulation thickness | Steel Wire diameter | Sheath thickness | Approximate outer diameter | Approx. weight |
Max.D.C resistance of conductor(20℃) | Current carrying capacity | |
mm2 | mm | mm | mm | mm | kg/km | Ω/km | In Air(A) | In Ground(A) |
5X2.5 | 0.7 | 1.25 | 1.8 | 17.9 | 645 | 7.41 | 20 | 27 |
5X4 | 0.7 | 1.25 | 1.8 | 19.1 | 770 | 4.61 | 26 | 36 |
5X6 | 0.7 | 1.25 | 1.8 | 20.5 | 925 | 3.08 | 33 | 45 |
5X10 | 0.7 | 1.6 | 1.8 | 24.6 | 1417 | 1.83 | 46 | 60 |
5X16 | 0.7 | 1.6 | 1.8 | 27.6 | 1812 | 1.15 | 59 | 77 |
5X25 | 0.9 | 1.6 | 1.9 | 32.2 | 2460 | 0.727 | 77 | 98 |
5X35 | 0.9 | 1.6 | 2 | 34.1 | 3019 | 0.524 | 95 | 119 |
5X50 | 1 | 2 | 2.2 | 39.7 | 4166 | 0.387 | 119 | 144 |
5X70 | 1.1 | 2 | 2.3 | 44.9 | 5443 | 0.268 | 151 | 175 |
5X95 | 1.1 | 2.5 | 2.5 | 51.3 | 7485 | 0.193 | 186 | 210 |
5X120 | 1.2 | 2.5 | 2.7 | 55.9 | 9026 | 0.153 | 217 | 242 |
5X150 | 1.4 | 2.5 | 2.8 | 61.4 | 10912 | 0.124 | 245 | 270 |
5X185 | 1.6 | 2.5 | 3 | 67.6 | 13119 | 0.0991 | 284 | 305 |
5X240 | 1.7 | 2.5 | 3.3 | 74.8 | 16427 | 0.0754 | 336 | 350 |
5X300 | 1.8 | 3.15 | 3.5 | 83.2 | 20915 | 0.0601 | 389 | 396 |
0.6/1kV-3+1 core copper conductor XLPE insulated steel wire armored PVC sheathed power cable | ||||||||
Nominal cross sectional area | Insulation thickness | Steel Wire diameter | Sheath thickness | Approximate outer diameter | Approx. weight |
Max.D.C resistance of conductor(20℃) | Current carrying capacity | |
mm2 | mm | mm | mm | mm | kg/km | Ω/km | In Air(A) | In Ground(A) |
3X4+1X2.5 | 0.7/0.7 | 1.25 | 1.8 | 17.8 | 873 | 4.61/7.41 | 26 | 36 |
3X6+1X4 | 0.7/0.7 | 1.25 | 1.8 | 19.1 | 764 | 3.08/4.61 | 33 | 45 |
3X10+1X6 | 0.7/0.7 | 1.25 | 1.8 | 21.6 | 1002 | 1.83/3.08 | 46 | 60 |
3X16+1X10 | 0.7/0.7 | 1.6 | 1.8 | 25.1 | 1475 | 1.15/1.83 | 59 | 77 |
3X25+1X16 | 0.9/0.7 | 1.6 | 1.8 | 28.7 | 2101 | 0.727/1.15 | 77 | 98 |
3X35+1X16 | 0.9/0.7 | 1.6 | 1.8 | 30 | 2300 | 0.524/1.15 | 95 | 119 |
3X50+1X25 | 1/0.9 | 1.6 | 2 | 34.1 | 2945 | 0.387/0.727 | 119 | 144 |
3X70+1X35 | 1.1/0.9 | 2 | 2.1 | 39.2 | 4131 | 0.268/0.524 | 151 | 175 |
3X95+1X50 | 1.1/1.0 | 2 | 2.3 | 43.2 | 5199 | 0.193/0.387 | 186 | 210 |
3X120+1X70 | 1.2/1.1 | 2.5 | 2.4 | 48.8 | 6827 | 0.153/0.268 | 217 | 242 |
3X150+1X70 | 1.4/1.1 | 2.5 | 2.6 | 52.9 | 7915 | 0.124/0.268 | 245 | 270 |
3X185+1X95 | 1.6/1.1 | 2.5 | 2.7 | 57.8 | 9655 | 0.0991/0.193 | 284 | 305 |
3X240+1X120 | 1.7/1.2 | 2.5 | 2.9 | 64.1 | 11988 | 0.0754/0.153 | 336 | 350 |
3X300+1X150 | 1.8/1.4 | 2.5 | 3.1 | 69.8 | 14475 | 0.0601/0.124 | 389 | 396 |
0.6/1kV-4+1 core copper conductor XLPE insulated steel wire armored PVC sheathed power cable | ||||||||
Nominal cross sectional area | Insulation thickness | Steel Wire diameter | Sheath thickness | Approximate outer diameter | Approx. weight |
Max.D.C resistance of conductor(20℃) | Current carrying capacity | |
mm2 | mm | mm | mm | mm | kg/km | Ω/km | In Air(A) | In Ground(A) |
4X4+1X2.5 | 0.7/0.7 | 1.25 | 1.8 | 18.9 | 731 | 4.61/7.41 | 26 | 36 |
4X6+1X4 | 0.7/0.7 | 1.25 | 1.8 | 20.3 | 875 | 3.08/4.61 | 33 | 45 |
4X10+1X6 | 0.7/0.7 | 1.6 | 1.8 | 23.9 | 1295 | 1.83/3.08 | 46 | 60 |
4X16+1X10 | 0.7/0.7 | 1.6 | 1.8 | 27 | 1712 | 1.15/1.83 | 59 | 77 |
4X25+1X16 | 0.9/0.7 | 1.6 | 1.9 | 31.2 | 2322 | 0.727/1.15 | 77 | 98 |
4X35+1X16 | 0.9/0.7 | 1.6 | 1.9 | 32.8 | 2759 | 0.524/1.15 | 95 | 119 |
4X50+1X25 | 1/0.9 | 2 | 2.1 | 38.5 | 3860 | 0.387/0.727 | 119 | 144 |
4X70+1X35 | 1.1/0.9 | 2 | 2.3 | 43 | 5010 | 0.268/0.524 | 151 | 175 |
4X95+1X50 | 1.1/1.0 | 2.5 | 2.4 | 48.9 | 6850 | 0.193/0.387 | 186 | 210 |
4X120+1X70 | 1.2/1.1 | 2.5 | 2.6 | 54 | 8395 | 0.153/0.268 | 217 | 242 |
4X150+1X70 | 1.4/1.1 | 2.5 | 2.7 | 58.4 | 9745 | 0.124/0.268 | 245 | 270 |
4X185+1X95 | 1.6/1.1 | 2.5 | 2.9 | 64.4 | 11948 | 0.0991/0.193 | 284 | 305 |
4X240+1X120 | 1.7/1.2 | 2.5 | 3.1 | 71.1 | 14832 | 0.0754/0.153 | 336 | 350 |
4X300+1X150 | 1.8/1.4 | 3.15 | 3.4 | 78.9 | 18826 | 0.0601/0.124 | 389 | 396 |
0.6/1kV-3+2 core copper conductor XLPE insulated steel wire armored PVC sheathed power cable | ||||||||
Nominal cross sectional area | Insulation thickness | Steel Wire diameter | Sheath thickness | Approximate outer diameter | Approx. weight |
Max.D.C resistance of conductor(20℃) | Current carrying capacity | |
mm2 | mm | mm | mm | mm | kg/km | Ω/km | In Air(A) | In Ground(A) |
3X4+2X2.5 | 0.7/0.7 | 1.25 | 1.8 | 18.6 | 705 | 4.61/7.41 | 26 | 36 |
3X6+2X4 | 0.7/0.7 | 1.25 | 1.8 | 20 | 845 | 3.08/4.61 | 33 | 45 |
3X10+2X6 | 0.7/0.7 | 1.25 | 1.8 | 22.5 | 1109 | 1.83/3.08 | 46 | 60 |
3X16+2X10 | 0.7/0.7 | 1.6 | 1.8 | 26.5 | 1630 | 1.15/1.83 | 59 | 77 |
3X25+2X16 | 0.9/0.7 | 1.6 | 1.8 | 30.2 | 2185 | 0.727/1.15 | 77 | 98 |
3X35+2X16 | 0.9/0.7 | 1.6 | 1.9 | 31.3 | 2505 | 0.524/1.15 | 95 | 119 |
3X50+2X25 | 1/0.9 | 2 | 2.1 | 37 | 3531 | 0.387/0.727 | 119 | 144 |
3X70+2X35 | 1.1/0.9 | 2 | 2.2 | 41.1 | 4572 | 0.268/0.524 | 151 | 175 |
3X95+2X50 | 1.1/1.0 | 2 | 2.4 | 45.8 | 5841 | 0.193/0.387 | 186 | 210 |
3X120+2X70 | 1.2/1.1 | 2.5 | 2.6 | 52.1 | 7765 | 0.153/0.268 | 217 | 242 |
3X150+2X70 | 1.4/1.1 | 2.5 | 2.7 | 55.4 | 8758 | 0.124/0.268 | 245 | 270 |
3X185+2X95 | 1.6/1.1 | 2.5 | 2.8 | 60.8 | 10777 | 0.0991/0.193 | 284 | 305 |
3X240+2X120 | 1.7/1.2 | 2.5 | 3 | 67.4 | 13385 | 0.0754/0.153 | 336 | 350 |
3X300+2X150 | 1.8/1.4 | 2.5 | 3.2 | 73.6 | 16100 | 0.0601/0.124 | 389 | 396 |