NA2XBY Cable

Low Voltage Aluminum XLPE Cable with Double Galvanized Steel Tape Armoured

Conductor: Aluminum

Insulation: XLPE

Armour: Double galvanized steel tape

Sheath: Polyvinylchloride compound PVC 5V-90

Voltage : 0.6/1kV

Package : Export wooden drum & iron wooden drum or as customer require

Email: manager@hdcable.com.cn

 NA2XBY Cable Application

NA2XBY cable is suitable for AC 50Hz power and distribution lines with rated voltage of 0.6/1kV, which can be used in fixed industrial power applications, underground tunnels, etc. Using steel wire armour offers great mechanical protection, making it rigid with a large radius.

 NA2XBY Cable Standards:

 
IEC 60228 Conductors
IEC 60502-1 Power cables with extruded insulation and their accessories for rated voltages from 1kV(Um=1.2kV) up to 30kV(Um=36kV) - Part 1: Cables for rated voltages of 1 kV(Um=1.2kV) and 3 kV(Um=3.6kV)
CONSTRUCTION :

 NA2XBY Cable Construction

nayby structure

Conductor: Copper or aluminum, Class 1: solid conductor, or Class 2: stranded conductor
Insulation:Cross-linked polyethylene XLPE

Filler: Non-hygroscopic material
Binder tape: Non-hygroscopic material
Inner sheath: Polyvinyl chloride PVC
Armour: Double galvanized steel tape
Outer sheath: Polyvinyl chloride PVC
TECHNICAL :
Voltage Rating Uo/U (Um) 0.6/1 (1.2)kV
Nominal Voltage DC (core-earth/core-core) :1.8/1.8kV
Test Voltage:4kV
Temperature Rating:
Flexed: 5°C to +90°C
Fixed: -35°C to +90°C
Maximum Short Circuit Temperature:
+250°C (max 5 seconds)
Minimum Bend Radius:
Single core: 15 x overall diameter
Multi core: 12 x overall diameter
PARAMETER :
0.6/1kV-1 core aluminum conductor XLPE insulated steel tape armored PVC sheathed power cable
Nominal cross sectional area Insulation thickness Non-magnetic steel tape thickness  Sheath thickness Approximate outer diameter Approx. Max.D.C resistance of conductor(20℃) Current carrying capacity 
weight
mm2 mm mm mm mm kg/km Ω/km In Air(A) In Ground(A)
1X10 0.7 0.2 1.8 11.8 206 3.08 58 47
1X16 0.7 0.2 1.8 12.9 247 1.91 75 62
1X25 0.9 0.2 1.8 14.6 310 1.2 100 78
1X35 0.9 0.2 1.8 15.2 352 0.868 120 94
1X50 1 0.2 1.8 16.7 423 0.641 145 110
1X70 1.1 0.2 1.8 18.5 523 0.443 190 135
1X95 1.1 0.2 1.8 20.1 629 0.32 235 160
1X120 1.2 0.2 1.8 21.7 738 0.253 270 185
1X150 1.4 0.2 1.8 23.7 877 0.206 310 205
1X185 1.6 0.2 1.8 25.7 1031 0.164 355 235
1X240 1.7 0.2 1.8 28 1254 0.125 - -
1X300 1.8 0.2 1.9 31 1495 0.1 - -
1X400 2 0.2 2 35 1904 0.0778 - -
                 
0.6/1kV-2 core aluminum conductor XLPE insulated steel tape armored PVC sheathed power cable
Nominal cross sectional area Insulation thickness Non-magnetic steel tape thickness  Sheath thickness Approximate outer diameter Approx. Max.D.C resistance of conductor(20℃) Current carrying capacity 
weight
mm2 mm mm mm mm kg/km Ω/km In Air(A) In Ground(A)
2X2.5 0.7 0.2 1.8 13.4 236 12.1 - 23
2X4 0.7 0.2 1.8 14.3 269 7.41 - 30
2X6 0.7 0.2 1.8 15.3 307 4.61 - 38
2X10 0.7 0.2 1.8 17.8 397 3.08 50 47
2X16 0.7 0.2 1.8 20 493 1.91 64 62
2X25 0.9 0.2 1.8 23.3 643 1.2 86 78
2X35 0.9 0.2 1.8 24.6 738 0.868 105 94
2X50 1 0.2 1.8 27.2 896 0.641 125 110
2X70 1.1 0.2 1.9 31.4 1164 0.443 165 135
2X95 1.1 0.2 2 35.5 1480 0.32 200 160
2X120 1.2 0.5 2.2 40.2 2164 0.253 235 185
2X150 1.4 0.5 2.3 44.2 2572 0.206 270 205
2X185 1.6 0.5 2.5 48.9 3089 0.164 310 235
                 
0.6/1kV-3 core aluminum conductor XLPE insulated steel tape armored PVC sheathed power cable
Nominal cross sectional area Insulation thickness Non-magnetic steel tape thickness  Sheath thickness Approximate outer diameter Approx. Max.D.C resistance of conductor(20℃) Current carrying capacity 
weight
mm2 mm mm mm mm kg/km Ω/km In Air(A) In Ground(A)
3X2.5 0.7 0.2 1.8 13.9 257 12.1 - 23
3X4 0.7 0.2 1.8 14.8 296 7.41 - 30
3X6 0.7 0.2 1.8 16 342 4.61 - 38
3X10 0.7 0.2 1.8 18.6 447 3.08 50 47
3X16 0.9 0.2 1.8 21 563 1.91 64 62
3X25 0.9 0.2 1.8 24.6 744 1.2 86 78
3X35 0.9 0.2 1.8 26 869 0.868 105 94
3X50 1 0.2 1.9 28.9 1074 0.641 125 110
3X70 1.1 0.2 2 33.9 1443 0.443 165 135
3X95 1.1 0.5 2.2 39 2183 0.32 200 160
3X120 1.2 0.5 2.3 42.7 2593 0.253 235 185
3X150 1.4 0.5 2.4 47.5 3155 0.206 270 205
3X185 1.6 0.5 2.6 52.1 3743 0.164 310 235
3X240 1.7 0.5 2.8 58.3 4641 0.125 365 260
3X300 1.8 0.5 2.9 63.6 5508 0.1 420 290
                 
0.6/1kV-4 core aluminum conductor XLPE insulated steel tape armored PVC sheathed power cable
Nominal cross sectional area Insulation thickness Non-magnetic steel tape thickness  Sheath thickness Approximate outer diameter Approx. Max.D.C resistance of conductor(20℃) Current carrying capacity 
weight
mm2 mm mm mm mm kg/km Ω/km In Air(A) In Ground(A)
4X2.5 0.7 0.2 1.8 14.7 288 12.1 - 23
4X4 0.7 0.2 1.8 15.8 334 7.41 - 30
4X6 0.7 0.2 1.8 17 384 4.61 - 38
4X10 0.7 0.2 1.8 20 509 3.08 50 47
4X16 0.9 0.2 1.8 22.7 649 1.91 64 62
4X25 0.9 0.2 1.8 26.7 880 1.2 86 78
4X35 0.9 0.2 1.8 28.3 1040 0.868 105 94
4X50 1 0.2 2.1 32 1365 0.641 125 110
4X70 1.1 0.5 2.1 38.5 2138 0.443 165 135
4X95 1.1 0.5 2.3 42.9 2638 0.32 200 160
4X120 1.2 0.5 2.4 47.4 3202 0.253 235 185
4X150 1.4 0.5 2.6 52.3 3847 0.206 270 205
4X185 1.6 0.5 2.7 57.5 4585 0.164 310 235
4X240 1.7 0.5 3 64.3 5709 0.125 365 260
4X300 1.8 0.5 3.1 70.3 6805 0.1 420 290
                 
0.6/1kV-5 core aluminum conductor XLPE insulated steel tape armored PVC sheathed power cable
Nominal cross sectional area Insulation thickness Non-magnetic steel tape thickness  Sheath thickness Approximate outer diameter Approx. Max.D.C resistance of conductor(20℃) Current carrying capacity 
weight
mm2 mm mm mm mm kg/km Ω/km In Air(A) In Ground(A)
5X2.5 0.7 0.2 1.8 15.6 321 12.1 - 23
5X4 0.7 0.2 1.8 16.8 376 7.41 - 30
5X6 0.7 0.2 1.8 18.2 443 4.61 - 38
5X10 0.7 0.2 1.8 21.6 592 3.08 50 47
5X16 0.7 0.2 1.8 24.6 763 1.91 64 62
5X25 0.9 0.2 1.8 29 1029 1.2 86 78
5X35 0.9 0.2 1.9 31 1236 0.868 105 94
5X50 1 0.2 2.1 35.7 1616 0.641 125 110
5X70 1.1 0.5 2.3 42.4 2528 0.443 165 135
5X95 1.1 0.5 2.4 47.2 3172 0.32 200 160
5X120 1.2 0.5 2.6 51.8 3801 0.253 235 185
5X150 1.4 0.5 2.7 57.6 4604 0.206 270 205
5X185 1.6 0.5 2.9 63.8 5574 0.164 310 235
5X240 1.7 0.5 3.2 70.7 6859 0.125 365 260
5X300 1.8 0.5 3.4 78 8305 0.1 420 290
                 
0.6/1kV-3+1core aluminum conductor XLPE insulated steel tape armored PVC sheathed power cable
Nominal cross sectional area Insulation thickness Non-magnetic steel tape thickness  Sheath thickness Approximate outer diameter Approx. Max.D.C resistance of conductor(20℃) Current carrying capacity 
weight
mm2 mm mm mm mm kg/km Ω/km In Air(A) In Ground(A)
3X4+1X2.5 0.7/0.7 0.2 1.8 15.5 318 7.41/12.1 - 30
3X6+1X4 0.7/0.7 0.2 1.8 16.8 371 4.61/7.41 - 38
3X10+1X6 0.7/0.7 0.2 1.8 19.3 478 3.08/4.61 50 47
3X16+1X10 0.7/0.7 0.2 1.8 22.1 615 1.91/3.08 64 62
3X25+1X16 0.9/0.7 0.2 1.8 25.1 794 1.2/1.91 86 78
3X35+1X16 0.9/0.7 0.2 1.8 26.8 926 0.868/1.91 105 94
3X50+1X25 1/0.9 0.2 1.9 30.2 1175 0.641/1.2 125 110
3X70+1X35 1.1/0.9 0.2 2 35.1 1570 0.443/0.868 165 135
3X95+1X50 1.1/1.0 0.5 2.2 40.4 2359 0.32/0.641 200 160
3X120+1X70 1.2/1.1 0.5 2.3 45 2886 0.253/0.443 235 185
3X150+1X70 1.4/1.1 0.5 2.5 49.1 3396 0.206/0.443 270 205
3X185+1X95 1.6/1.1 0.5 2.8 54.3 4070 0.164/0.32 310 235
3X240+1X120 1.7/1.2 0.5 2.8 59.1 4855 0.125/0.253 365 260
3X300+1X150 1.8/1.4 0.5 3 66 6028 0.1/0.206 420 290
                 
0.6/1kV-4+1core aluminum conductor XLPE insulated steel tape armored PVC sheathed power cable
Nominal cross sectional area Insulation thickness Non-magnetic steel tape thickness  Sheath thickness Approximate outer diameter Approx. Max.D.C resistance of conductor(20℃) Current carrying capacity 
weight
mm2 mm mm mm mm kg/km Ω/km In Air(A) In Ground(A)
4X4+1X2.5 0.7/0.7 0.2 1.8 16.3 365 7.41/12.1 - 30
4X6+1X4 0.7/0.7 0.2 1.8 17.7 429 4.61/7.41 - 38
4X10+1X6 0.7/0.7 0.2 1.8 20.3 561 3.08/4.61 50 47
4X16+1X10 0.7/0.7 0.2 1.8 24 728 1.91/3.08 64 62
4X25+1X16 0.9/0.7 0.2 1.8 28.1 974 1.2/1.91 86 78
4X35+1X16 0.9/0.7 0.2 1.9 29.6 1134 0.868/1.91 105 94
4X50+1X25 1/0.9 0.2 2 34 1505 0.641/1.2 125 110
4X70+1X35 1.1/0.9 0.5 2.2 40.3 2351 0.443/0.868 165 135
4X95+1X50 1.1/1.0 0.5 2.3 44.8 2907 0.32/0.641 200 160
4X120+1X70 1.2/1.1 0.5 2.6 50.2 3588 0.253/0.443 235 185
4X150+1X70 1.4/1.1 0.5 2.8 54.6 4215 0.206/0.443 270 205
4X185+1X95 1.6/1.1 0.5 2.9 60.5 5133 0.164/0.32 310 235
4X240+1X120 1.7/1.2 0.5 3 67.1 6289 0.125/0.253 365 260
4X300+1X150 1.8/1.4 0.5 3.2 73.7 7544 0.1/0.206 420 290
                 
0.6/1kV-3+2 core aluminum conductor XLPE insulated steel tape armored PVC sheathed power cable
Nominal cross sectional area Insulation thickness Non-magnetic steel tape thickness  Sheath thickness Approximate outer diameter Approx. Max.D.C resistance of conductor(20℃) Current carrying capacity 
weight
mm2 mm mm mm mm kg/km Ω/km In Air(A) In Ground(A)
3X4+2X2.5 0.7/0.7 0.2 1.8 16.6 354 7.41/12.1 - 30
3X6+2X4 0.7/0.7 0.2 1.8 18 416 4.61/7.41 - 38
3X10+2X6 0.7/0.7 0.2 1.8 20.9 531 3.08/4.61 50 47
3X16+2X10 0.7/0.7 0.2 1.8 24 694 1.91/3.08 64 62
3X25+2X16 0.9/0.7 0.2 1.8 28.1 920 1.2/1.91 86 78
3X35+2X16 0.9/0.7 0.2 1.9 29.6 1034 0.868/1.91 105 94
3X50+2X25 1/0.9 0.2 2 34 1400 0.641/1.2 125 110
3X70+2X35 1.1/0.9 0.5 2.2 40.3 2153 0.443/0.868 165 135
3X95+2X50 1.1/1.0 0.5 2.3 44.8 2658 0.32/0.641 200 160
3X120+2X70 1.2/1.1 0.5 2.5 50.2 3329 0.253/0.443 235 185
3X150+2X70 1.4/1.1 0.5 2.6 54.6 3790 0.206/0.443 270 205
3X185+2X95 1.6/1.1 0.5 2.8 60.5 4575 0.164/0.32 310 235
3X240+2X120 1.7/1.2 0.5 3 67.1 5564 0.125/0.253 365 260
3X300+2X150 1.8/1.4 0.5 3.2 73.7 6801 0.1/0.206 420 290