What is TTU CABLE
The TTU cable is a copper conductor with PE / XLPE insulation and PVC sheath.
The TTU cable type conductors (600V, 2 kV) are wired and are built with soft-tempered copper, they are also insulated with a uniform layer of thermoplastic polyethylene (PE) or cross-linked polyethylene (XLPE) material resistant to humidity and heat, on which a polyvinyl chloride (PVC) protective cover. They are always supplied in black color and with different forms of packaging.
CABLE TTU APPLICATIONS
TTU cable type copper conductors are used for power and lighting circuits in industrial and commercial buildings, they are especially suitable for outdoor or directly buried installations. This type of conductor can be used in dry and humid places, its maximum operating temperature is 75℃ and 90℃ and its service voltage for all applications is 0.6 or 2 kV.
TTU Cable 600 Volt, 75℃, Copper Wire Specification
SIZE |
CROSS SECTION |
STRANDING |
INSULATION THICKNESS |
JACKET THICKNESS |
EXTERNAL DIAMETER |
TOTAL WEIGHT |
AMPACITY |
14 |
2.06 |
1x1.62 |
0.81 |
0.38 |
4.14 |
31.3 |
20 |
12 |
3.30 |
1x2.05 |
0.81 |
0.38 |
4.54 |
44.7 |
25 |
10 |
5.26 |
1x2.59 |
0.81 |
0.38 |
5.10 |
62.6 |
35 |
8 |
8,37 |
7 x 1,23 |
1,14 |
0,38 |
6,73 |
109,0 |
50 |
6 |
13,30 |
7 x 1,55 |
1,14 |
0,76 |
8,45 |
170,0 |
65 |
4 |
21,15 |
7 x 1,96 |
1,14 |
0,76 |
9,68 |
301,0 |
85 |
2 |
33,62 |
7 x 2,47 |
1,14 |
0,76 |
11,21 |
376,0 |
115 |
1 |
42,36 |
7 x 2,78 |
1,40 |
1,14 |
13,42 |
461,5 |
130 |
1/0 |
53,49 |
19 x 1,89 |
1,40 |
1,14 |
14,53 |
609,0 |
150 |
2/0 |
67,43 |
19 x 2,12 |
1,40 |
1,14 |
15,68 |
747,0 |
175 |
3/0 |
85,01 |
19 x 2,39 |
1,40 |
1,14 |
17,03 |
915,0 |
200 |
4/0 |
107,20 |
19 x 2,68 |
1,40 |
1,14 |
18,48 |
1132,0 |
230 |
250 |
127,00 |
37 x 2,09 |
1,65 |
1,65 |
21,23 |
1390,0 |
255 |
300 |
152,00 |
37 x 2,29 |
1,65 |
1,65 |
22,63 |
1641,0 |
285 |
350 |
177,00 |
37 x 2,47 |
1,65 |
1,65 |
23,89 |
1889,0 |
310 |
400 |
203,00 |
37 x 2,64 |
1,65 |
1,65 |
25,08 |
2137,0 |
335 |
500 |
253,00 |
37 x 2,95 |
1,65 |
1,65 |
27,25 |
2627,0 |
380 |
600 |
304,00 |
37 x 3,23 |
2,03 |
1,65 |
29,97 |
3144,0 |
420 |
650 |
329,00 |
37 x 3,37 |
2,03 |
1,65 |
30,95 |
3409,0 |
440 |
700 |
355,00 |
37 x 3,49 |
2,03 |
1,65 |
31,79 |
3593,0 |
460 |
750 |
380.99 |
61x2.82 |
2.03 |
1.65 |
32.18 |
3854.0 |
475 |
1000 |
506.04 |
61x3.25 |
2.03 |
1.65 |
35.94 |
5045.2 |
545 |
TTU Cable 2000 Volt, 90℃, Copper Wire Specification
SIZE |
CROSS SECTION |
STRANDING |
INSULATION THICKNESS |
JACKET THICKNESS |
EXTERNAL DIAMETER |
TOTAL WEIGHT |
AMPACITY |
14 |
2.06 |
1x1.62 |
1,14 |
0.38 |
4.67 |
42 |
20 |
12 |
3.30 |
1x2.05 |
1,14 |
0.38 |
5.09 |
56 |
25 |
10 |
5.26 |
1x2.59 |
1,14 |
0.38 |
5.63 |
78 |
35 |
8 |
8,37 |
7 x 1,23 |
1,40 |
0,38 |
7.25 |
105 |
50 |
6 |
13,30 |
7 x 1,55 |
1,40 |
0,76 |
9 |
176 |
65 |
4 |
21,15 |
7 x 1,96 |
1,40 |
0,76 |
10.2 |
257 |
85 |
2 |
33,62 |
7 x 2,47 |
1,40 |
0,76 |
11.73 |
382 |
115 |
1 |
42,36 |
7 x 2,78 |
1,65 |
1,14 |
13.92 |
500 |
130 |
1/0 |
53,49 |
19 x 1,89 |
1,65 |
1,14 |
15.03 |
613 |
150 |
2/0 |
67,43 |
19 x 2,12 |
1,65 |
1,14 |
16.23 |
751 |
175 |
3/0 |
85,01 |
19 x 2,39 |
1,65 |
1,14 |
17.53 |
924 |
200 |
4/0 |
107,20 |
19 x 2,68 |
1,65 |
1,14 |
18.98 |
1143 |
230 |
250 |
127,00 |
37 x 2,09 |
1,90 |
1,65 |
21.73 |
1405 |
255 |
300 |
152,00 |
37 x 2,29 |
1,90 |
1,65 |
23.13 |
1651 |
285 |
350 |
177,00 |
37 x 2,47 |
1,90 |
1,65 |
24.39 |
1901 |
310 |
400 |
203,00 |
37 x 2,64 |
1,90 |
1,65 |
25.58 |
2130 |
335 |
500 |
253,00 |
37 x 2,95 |
1,90 |
1,65 |
27.75 |
2639 |
380 |
600 |
304,00 |
37 x 3,23 |
2,29 |
1,65 |
30.49 |
3150 |
420 |
650 |
329,00 |
37 x 3,37 |
2,29 |
1,65 |
31.47 |
3400 |
440 |
700 |
355,00 |
37 x 3,49 |
2,29 |
1,65 |
32.31 |
3630 |
460 |
750 |
380.99 |
61x2.82 |
2.29 |
1.65 |
33.26 |
3878 |
475 |
1000 |
506.04 |
61x3.25 |
2.29 |
1.65 |
37.13 |
5080 |
545 |
Keywords: ttu cable, cable ttu, cable ttu 2/0, cable ttu 4/0, cable ttu 1/0, cable ttu 4, cable ttu 6, ttu 500mcm, ttu 600mcm