PVC Insulated Drop Service Wire DV
Conductors: Copper
Insulation: PVC
Temperature range during operation: -30°C – +70°C
Temperature range during installation: -20°C – +50°C
Minimum bending radius: 7.5 x Overall Diameter
Email: manager@hdcable.com.cn
It is chiefly used for drop-in from overhead distribution line, under A.C.600V grade, and very convenient for wiring, colour being easily identified.
It is weather proof and can be used for a long period without damage due to fire, electrical shock and other accidents.
Number of Core | Color |
2 Core | Black,Green or Black,Blue |
3 Core | Black,Green,Blue |
Parallel | Black |
Types | Symbols |
Duplex | DV-2R |
Triplex | DV-3R |
Two Core Flat Type | DV-2F |
Conductor | Nominal Insulation Thickness |
Overall Diameter |
Test Voltage |
Min. Insulation Resistance |
Max. Conductor Resistance at 20℃ |
Min. Tensile Load |
Approx. Weight |
Standard Length |
|||
Nominal Sectional Area |
Number & Diameter of Wire |
Outer Diameter | at 20℃ | at 60℃ | |||||||
mm2 | No./mm | mm | mm | mm | V/5min | Ω/km | Ω/km | N | kg/km | m | |
– | 1/2.0 | 2.0 | 0.8 | 7.2 | 1500 | 50 | 0.15 | 5.89 | 1,250 | 75 | 300 |
– | 1/2.6 | 2.6 | 1.0 | 9.2 | 1500 | 50 | 0.15 | 3.48 | 2,070 | 125 | 200 |
– | 1/3.2 | 3.2 | 1.2 | 11.5 | 1500 | 50 | 0.15 | 2.30 | 3,100 | 190 | 200 |
8 | 7/1.2 | 3.6 | 1.2 | 12.0 | 1500 | 50 | 0.15 | 2.43 | 3,190 | 205 | 300 |
14 | 7/1.6 | 4.8 | 1.4 | 15.5 | 2000 | 40 | 0.10 | 1.36 | 5,630 | 340 | 300 |
22 | 7/2.0 | 6.0 | 1.6 | 18.5 | 2000 | 40 | 0.10 | 0.832 | 4,100 | 525 | 300 |
38 | 7/2.6 | 7.8 | 1.8 | 23.0 | 2500 | 40 | 0.10 | 0.492 | 7,080 | 860 | 300 |
60 | 19/2.0 | 10.0 | 1.8 | 28.0 | 2500 | 30 | 0.07 | 0.306 | 10,600 | 1,310 | 300 |
Conductor |
Nominal |
Overall |
Test |
Min. |
Max. |
Min. |
Approx. |
Standard |
|||
Nominal |
Number & |
Outer Diameter |
at 20℃ |
at 60℃ |
|||||||
mm2 |
No./mm |
mm |
mm |
mm |
V/5min |
MΩ/km |
Ω/km |
N |
kg/km |
m |
|
– |
1/2.0 |
2.0 |
0.8 |
7.8 |
1500 |
50 |
0.15 |
5.89 |
1,250 |
115 |
300 |
– |
1/2.6 |
2.6 |
1.0 |
9.9 |
1500 |
50 |
0.15 |
3.48 |
2,070 |
190 |
200 |
– |
1/3.2 |
3.2 |
1.2 |
12.5 |
1500 |
50 |
0.15 |
2.30 |
3,100 |
285 |
200 |
8 |
7/1.2 |
3.6 |
1.2 |
13.0 |
1500 |
50 |
0.15 |
2.43 |
3,190 |
310 |
300 |
14 |
7/1.6 |
4.8 |
1.4 |
16.5 |
2000 |
40 |
0.10 |
1.36 |
5,630 |
510 |
300 |
22 |
7/2.0 |
6.0 |
1.6 |
20.0 |
2000 |
40 |
0.10 |
0.832 |
4,100 |
785 |
300 |
38 |
7/2.6 |
7.8 |
1.8 |
25.0 |
2500 |
40 |
0.10 |
0.492 |
7,080 |
1,290 |
300 |
60 |
19/2.0 |
10.0 |
1.8 |
30.0 |
2500 |
30 |
0.07 |
0.306 |
10,600 |
1,960 |
300 |
Conductor | Nominal Insulation Thickness |
Overall Diameter |
Test Voltage |
Min. Insulation Resistance at 20℃ |
Max. Conductor Resistance at 20℃ |
Min. Tensile Load |
Approx. Weight |
Standard Length |
|
Outer Diameter |
Outer Diameter |
||||||||
mm | mm | mm | mm | V/5min | Ω/km | Ω/km | N | kg/km | m |
2 | 3.142 | 0.8 | 3.6 x 7.90 | 1500 | 50 | 5.83 | 1,310 | 75 | 300 |
2.6 | 5.309 | 1.0 | 4.6 x 9.70 | 1500 | 50 | 3.45 | 2,190 | 125 | 200 |
3.2 | 8.042 | 1.2 | 5.6 x 12.0 | 1500 | 50 | 2.28 | 3,260 | 190 | 200 |