Three Core 12/20KV (Um=24KV) Unarmored Cable
Voltage: 12/20kV
Conductor: Copper or Aluminum
Operating Temperature: up to 90°C
Short Circuit Temperature: 250°C
Bending Radius: 15 x OD
Email: manager@hdcable.com.cn
XLPE(Cross linked polyethylene) insulated cable functions well for electricity transmission and distribution lines for its excellent electrical and physical properties, including the advantage of simplicity in construction, lightness in weight; convenience in application besides its excellent electrical, thermal, mechanical and anti-chemical corrosion properties.
GB/12706-2008, IEC60502,IEC 60228,IEC60332 BS 5467,BS 6622 , IS 1554 , IS 7098and ICEA S-66-524 etc.
Conductor: Plain annealed stranded compacted circular copper or aluminium conductor to IEC60228 class 2
Conductor Screen: Extruded semi-conductive compound
Insulation: XLPE (cross-linked polyethylene) rated at 90°C
Insulation Screen: Extruded semi-conductive compound
Metallic Screen: copper tape or a concentric layer of copper wires
Color for core identification: Red, Yellow ,Blue tape shall be applied between insulation screen and metallic screen ( The above identifying can be changed as user requirement)
Assembly : Three screened cores are laid up together ,if necessary filled with non-hygroscopic material compatible with insulation and covered with a layer of PVC sheath
Outer Sheath: PVC type ST2 to IEC 60502 or PE ,LSZH
Specification |
Outer diameter |
Nominal thickness of insulation |
Nominal sheath thickness |
Approx. Outer diameter of cable |
Approx. Weight of cable |
Ampacity of cable |
||||
Air |
Soil |
|||||||||
CU |
AL |
Cu |
Al |
Cu |
Al |
|||||
mm2 |
mm |
mm |
mm |
mm |
kg/km |
kg/km |
A |
A |
A |
A |
3×25 |
6.0 |
5.5 |
2.6 |
49.9 |
2491.3 |
2025.0 |
125 |
96 |
135 |
105 |
3×35 |
7.0 |
5.5 |
2.7 |
52.3 |
2922.3 |
2269.4 |
150 |
115 |
160 |
125 |
3×50 |
8.4 |
5.5 |
2.8 |
55.5 |
3536.9 |
2604.2 |
175 |
135 |
190 |
150 |
3×70 |
10.0 |
5.5 |
2.9 |
59.1 |
4314.1 |
3008.3 |
220 |
170 |
235 |
185 |
3×95 |
11.5 |
5.5 |
3.0 |
62.6 |
5243.6 |
3471.5 |
265 |
205 |
285 |
220 |
3×120 |
13.0 |
5.5 |
3.1 |
66.1 |
6142.2 |
3903.7 |
305 |
235 |
320 |
250 |
3×150 |
14.5 |
5.5 |
3.2 |
69.5 |
7211.1 |
4413.0 |
350 |
270 |
365 |
285 |
3×185 |
16.2 |
5.5 |
3.3 |
73.4 |
8423.3 |
4972.4 |
395 |
310 |
410 |
320 |
3×240 |
18.4 |
5.5 |
3.5 |
78.5 |
10279.2 |
5802.3 |
465 |
365 |
475 |
370 |
3×300 |
20.5 |
5.5 |
3.6 |
83.3 |
12247.7 |
6651.5 |
530 |
415 |
535 |
420 |
3×400 |
23.5 |
5.5 |
3.9 |
90.2 |
15418.2 |
7956.7 |
615 |
485 |
605 |
480 |
Nominal section area (mm2) |
Copper conductor(Ω/km) |
Aluminum conductor(Ω/km) |
1.5 |
12.1 |
- |
2.5 |
7.41 |
12.1 |
4 |
4.61 |
7.41 |
6 |
3.08 |
4.61 |
10 |
1.83 |
3.08 |
16 |
1.15 |
1.91 |
25 |
0.727 |
1.20 |
35 |
0.524 |
0.868 |
50 |
0.387 |
0.641 |
70 |
0.268 |
0.443 |
95 |
0.193 |
0.320 |
120 |
0.153 |
0.253 |
150 |
0.124 |
0.206 |
185 |
0.0991 |
0.164 |
240 |
0.0754 |
0.125 |
300 |
0.0601 |
0.100 |
400 |
0.0470 |
0.0778 |
500 |
0.0366 |
0.0605 |
630 |
0.0283 |
0.0469 |
Max. Permissible short-circuit current for conductor (reference value)
Nominal section area (mm2) |
Maximum permissible short-circuit current for conductor(1s)(KA) |
|
Copper conductor |
Aluminum conductor |
|
1.5 |
0.12 |
0.13 |
2.5 |
0.32 |
0.22 |
4 |
0.50 |
0.34 |
6 |
0.76 |
0.51 |
10 |
1.51 |
0.99 |
16 |
2.39 |
1.56 |
25 |
3.69 |
2.42 |
35 |
5.15 |
3.37 |
50 |
7.31 |
4.79 |
70 |
10.2 |
6.68 |
95 |
13.8 |
9.03 |
120 |
17.4 |
11.4 |
150 |
21.7 |
14.2 |
185 |
26.7 |
17.5 |
240 |
34.6 |
22.6 |
300 |
43.1 |
28.2 |
400 |
57.4 |
37.65 |
500 |
71.7 |
47.0 |
630 |
88.8 |
58.0 |