×
Send message
SEND
RESET
+86 371 60975619
manager@hdcable.com.cn
+8613290961076
Triplex Cable Aluminum Conductor Overhead Service Drop Cable Wire 600V

Triplex Cable—Aluminium Service Drop Cable Wire

Conductor: Soft 1350-H19 Aluminum Conductor

Insulation: Cross-linked Polyethylen

Voltage: 600V

Number of cores: Triplex

Package : Export wooden drum & iron wooden drum or as customer require

Email: manager@hdcable.com.cn

triplex-overhead-service-drop
文件类型: .pdf triplex-overhead-service-drop.pdf

Triplex Overhead Service Drop Cable Wire Application


Triplex aluminum wire has three conductors, with one of them being for neutral path, and two electrodes. The aluminum triplex cable is an electrical cable meant for power distributions from the utility lines to the consumer’s premises through the weather head. It has an operational voltage rating at 600 V and the maximum temperature rating of 75°C. A bare messenger wire of this electrical cable is bonded closely on the two insulated aluminum conductors, which are individually insulated with black cross-linked polyethylene for protection.

Triplex Overhead Service Drop Cable Wire Standard

• B-230 Aluminum Wire, 1350-H19 for Electrical Purposes.
• B-231 Aluminum Conductors, Concentric-Lay-Stranded.
• B-232 Aluminum Conductors, Concentric-Lay-Stranded, Coated Steel Reinforced (ACSR).
• B-399 Concentric-Lay-Stranded 6201-T81 Aluminum Alloy Conductors.
• ICEA S-76-474-Neutral-supported Power Cable Assemblies With Weather-Resistant Extruded Insulation Rated 600Volts

CONSTRUCTION :

  Triplex Overhead Service Drop Cable Wire Construction

Phase Conductor

Strand or Compressed 1350-H19 Series Aluminum Conductor.

Neutral(Messenger )Conductor

Bare ACSR messenger. Optional constructions include a messenger of AAC or 6201 alloy.

Insulation

Black Cross Linked Polyethylene (XLP) Insulation.




TECHNICAL DATA :

 Triplex Overhead Service Drop Cable Wire Technical Data

Rated voltage

V

600

Test voltage

Veff kV/Hz

4/50

Laying temperature

°C

min. -5

Operating temperature

°C

-30 ~ +90

Conductor temperature

°C

max. +90

Short-circuit temperature

°C/s

max. +250 /5

Bending radius (min.)

mm

20 × Ø of cable

 
PARAMETER :
Triplex Cable——Aluminium Service Drop Cable Wire Parameter

AAC Neutral-Messenger

Code Word

Phase Conductor

Bare Neutral Messenger

Weight Per 1000 ft. (lbs.)

Allowable Ampacities+

Size (AWG)

Stranding

Covering Thickness (mils.)

Size (AWG)

Stranding

Rated Strength (lbs.)

POLY

XLP

POLY

XLP

Patella

6

7

45

6

7

563

103

103

70

85

Oyster

4

7

45

4

7

881

156

160

90

115

Clam

2

7

45

2

7

1350

232

238

120

150

Murex

1/0

7

60

1/0

7

1990

373

383

160

205

Purpura

1/0

19

60

1/0

7

1990

370

380

160

205

Nassa

2/0

7

60

2/0

7

2510

461

472

185

235

Trophon

2/0

19

60

2/0

7

2510

456

467

185

235

Melita

3/0

19

60

3/0

19

3310

562

562

215

275

Portunus

4/0

19

60

4/0

19

4020

696

696

245

315

Nannynose

336.4

19

80

336.4

19

6146

1118

1118

325

420

 ACSR Neutral-Messenger

Code Word

Phase Conductor

Bare Neutral Messenger

Weight Per 1000 ft. (lbs.)

Allowable Ampacities+

Size (AWG)

Stranding

Covering Thickness (mils.)

Size (AWG)

Stranding

Rated Strength (lbs.)

POLY

XLP

POLY

XLP

Paludina

6

1

45

6

6/1

1190

109

110

70

85

Voluta

6

7

45

6

6/1

1190

116

118

70

85

Scallop

4

1

45

6

6/1

1190

143

146

90

115

Whelk

4

1

45

4

6/1

1860

165

169

90

115

Strombus

4

7

45

6

6/1

1190

156

160

90

115

Periwinkle

4

7

45

4

6/1

1860

172

176

90

115

Cockle

2

7

45

4

6/1

1860

227

233

120

150

Conch

2

7

45

2

6/1

2850

261

267

120

150

Janthina

1/0

7

60

2

6/1

2853

365

376

160

205

Neritina

1/0

7

60

1/0

6/1

4380

419

430

160

205

Ranella

1/0

19

60

2

6/1

2853

362

372

160

205

Cenia

1/0

19

60

1/0

6/1

4380

416

428

160

205

Cavolinia

2/0

7

60

1

6/1

3550

451

462

185

235

Runcina

2/0

7

60

2/0

6/1

5310

519

530

185

235

Clio

2/0

19

60

1

6/1

3550

437

444

185

235

Triton

2/0

19

60

2/0

6/1

5310

514

526

185

235

Aega

3/0

19

60

1/0

6/1

4380

549

559

215

275

Mursia

3/0

19

60

3/0

6/1

6620

626

633

215

275

Cerapus

4/0

19

60

2/0

6/1

5310

670

678

245

315

Zuzara

4/0

19

60

4/0

6/1

8350

777

785

245

315

Limpet

336.4

19

80

336.4

18/1

8680

1147

1161

325

420

6201 Alloy Neutral-Messenger

Code Word

Phase Conductor

Bare Neutral Messenger

Weight Per 1000 ft. (lbs.)

Allowable Ampacities+

Size (AWG)

Stranding

Covering Thickness (mils.)

ACSR Equivalent (AWG)

Stranding

Rated Strength (lbs.)

POLY

XLP

POLY

XLP

Minex

6

1

45

6

7

1110

101

102

70

85

Hippa

6

7

45

6

7

1110

105

107

70

85

Artemia

4

1

45

6

7

1110

132

134

90

115

Prawn

4

1

45

4

7

1760

152

154

90

115

Crab

4

7

45

6

7

1110

141

144

90

115

Barnacle

4

7

45

4

7

1760

157

160

90

115

Solaster

2

7

45

4

7

1760

212

216

120

150

Shrimp

2

7

45

2

7

2800

238

243

120

150

Sandcrab

1/0

7

60

2

7

2800

341

348

160

205

Gammarus

1/0

7

60

1/0

7

4460

384

390

160

205

Echinus

1/0

19

60

2

7

2800

336

342

160

205

Leda

1/0

19

60

1/0

7

4460

378

384

160

205

Dungenese

2/0

7

60

2/0

7

5390

474

481

185

235

Cyclops

2/0

19

60

2/0

7

5390

467

473

185

235

Fulgar

3/0

19

60

1/0

7

4460

518

525

215

275

Flustra

3/0

19

60

3/0

7

6790

588

596

215

275

Arca

4/0

19

60

2/0

7

5390

632

640

245

315

Lepas

4/0

19

60

4/0

7

8560

716

725

245

315

+Conductor temperature of 90°C for XLP, 75°C for Poly; ambient temperature of 40°C; emissivity 0.9; 2 ft./sec. wind in sun.

 
Send message
SEND
RESET
Related products