XLPE Insulated 3+2 Cores Copper Cable 3X35+2X16mm2

XLPE Insulated, PVC Sheathed Unarmoured 3+2 Cores Copper Cable 3X35+2X16mm2, 0.6/1kV

Number of Cores: 3+2

Cross section area: 3X35+2X16mm2

Conductor: Copper

Voltage: 0.6/1kV

Package : Export wooden drum & iron wooden drum or as customer require

Email: manager@hdcable.com.cn

XLPE 3X35+2X16mm2 Copper Cable Application

XLPE insulated 3+2 cores power cables are normally used in power transmission and distribution systems. The 3+2 cores XLPE cable is referred to as IEC60502 CU/XLPE/PVC 0.6/1KV.

These cables are used for outdoor and indoor installations in damp and wet applications. They are normally used for power distribution in urban networks, industrial plants and energy distribution. For mains, submains and subcircuits unenclosed, enclosed in conduit, buried direct or in underground ducts for buildings and industrial plants where not subject to mechanical damage. Suitable where space is at a premium.
 
STANDARDS :

XLPE 3X35+2X16mm2 Copper Cable Standards:


IEC 60228 Conductors
IEC 60502-1 Power cables with extruded insulation and their accessories for rated voltages from 1kV(Um=1.2kV) up to 30kV(Um=36kV) - Part 1: Cables for rated voltages of 1 kV(Um=1.2kV) and 3 kV(Um=3.6kV)

 
CONSTRUCTION :

XLPE 3X35+2X16mm2 Copper Cable Construction

1. Conductor: Copper , Class 2: stranded conductor
2. Insulation: Cross-linked polyethylene XLPE
3. Filler: Non-hygroscopic material
4. Binder tape: Non-hygroscopic material
5. Outer sheath: Polyvinyl chloride PVC

xlpe 3X2.5+2X1.5mm2 cable
PARAMETER :
XLPE 3X35+2X16mm2 Copper Cable Parameter
Cable Type: CU/XLPE/PVC
Operating voltage, U0 / U (V): 600/1000
Number of cores: 3+2
Phase Conductor Nominal Area (mm2): 35
Earth Conductor Nominal Area (mm2):
16
Phase Conductor Stranding: 7
Earth Conductor Stranding:
7
Phase Conductor Insulation Thickness (mm): 0.9
Earth Conductor Insulation Thickness (mm):
0.7
Sheath Thickness (mm): 1.8
Cable Overall Diameter (O.D.) (mm): 26.8
Cable Weight Per 1000 Meters (kg): 1420
Phase Conductor Resistance DC 20°C Per 1000 Meters (Ω): 0.524
Earth Conductor Resistance DC 20°C Per 1000 Meters (Ω):
1.15
Allowable Ampacity in Air (Amps): 135
Allowable Ampacity  in Ground (Amps): 170
Test Voltage:
3.5kV for 5 minutes
Operating temperature (°C) : -15 to +90
Final short circuit temperature (°C):
250